Technical Information
- Redundant modules allow both modules to control the process. Role reversal is automatic on detected failures
- Interfaces The MESH control network (100 Mbps) to the 2 Mbps Module Fieldbus for 200 Series (or equivalent) FBMs or to the 268 Kbps Fieldbus for 100 Series (or equivalent) FBMs
- Direct multi mode fiber optic connection to The MESH control network
- Uses soft letterbug configurable via the I/A Series® Letterbug Configurator
- Harsh (Class G3 - ISA S71.04) contamination protection
- Monitored by standard I/A Series System Management displays
- An FCM100E communicates with up to 32 200 Series FBMs or up to 64 100 Series FBMs.
- “CE” logo marked on product.
|
|
|
|
|
|
|