The
IRIS Model 600 Ultra Flame Rod is a reliable Flame Detecting system based on the proven principle of measuring rectified
current flow through a flame rod when a flame touches it.
An AC voltage is
applied to the flame rod; when a flame touches the rod, a rectified
current flows from the rod through the flame to the ground of the burner.
The Model 600 Flame Detector measures the rectified current and closes
the flame relay if the current exceeds the value for the flame-on
set-point.
If the current flow drops below the value for the flame-off
set-point, the flame relay opens.
A visual display indicates whether or
not the flame relay is on and the relative signal strength, i.e., the DC
current flow through the flame.