SL-3V Specifications |
Measurement range (Vrms)
|
0Vac to 500Vrms (Ph Ph) or 0V to 300Vrms (Ph N)
|
Maximum channel input voltage
|
500Vrms (Ph Ph), 300Vrms (Ph N) or 700Vpeak
|
Inputs (non-isolated inputs)
|
Three phase inputs (L1, L2 & L3) & Neutral (N), Non-isolated input channels
|
Input socket types
|
4mm shrouded banana plugs & sockets, each with insulated crocodile clip
|
Measurement accuracy
|
±1% of reading (10 bit) within 90Vac - 450Vrms (ph ph); else ±3%. (50/60Hz ±2%)
|
Vmax, Vmin, Imax & Imin time resolution
|
Always one cycle (50/60 Hz), independent of selected averaging period
|
Sampling frequency
|
16 samples per cycle 800Hz @ 50Hz or 960Hz @ 60Hz
|
Data recorded
|
Average voltage, max & min voltage-cycle-value during the averaging period
|
Memory capacity
|
192kB able to record 32,000 Voltage levels per phase
|
Memory type
|
Non-volatile SEEPROM
|
Memory - averaging period & duration
|
1 sec to 60 mins (1 sec gives 2 hrs logging, 60 min gives up to 300 days logging)
|
Real-time clock accuracy
|
Greater than 0.001%
|
Input Lead Length
|
Metric 2 metres Imperial/English 6 6 (6 feet, 6 inches)
|
Battery life (while plugged in)
|
Unlimited - mains powered & battery backup (8,000 hours, ~1 year while unpowered
|
Battery Type
|
Unit contains one 9V Alkaline batteries (E-Block, PP3, 1604A)
|
Communications Interface type
|
RS-232 serial, baud of 19,200
|
Electrosoft Software
|
Windows (9x, 2K, ME, NT & XP); 1024 x 768 min resolution
|
Environmental (temp & sealing)
|
-10C to +40C or +14°F to +104°F Indoor or protected environment only
|
Dimensions & Weight
|
Metric 145 x 89 x 46mm & 300g; Imperial/English - 6 x 3.5 x 2 & 0.6lbs
|
Standards
|
Recording - EN50160: 1994 - CAT III, maximum input voltage 600Vac
|